Proximity Switch - Ferrous » FS-GI Series

Proximity Switch for UL Listed for Ordinary Location - Multi Voltage AC/DC - SPCO/SPDT - 316L Stainless Steel
Certifications / Approvals

Proximity Switch for UL Ordinary Location, General Purpose use
This Proximity Switch has a 316L Stainless Steel Cylindrical with LED Indication housing with SPCO / SPDT (Form C) , volt free Palladium-Silver contacts. It has a maximum switching current of 250mA and can be used for switching multiple voltages in AC or DC. These switches are able to sense ferrous material, such as carbon steel or stainless steel (17/4 or 400 series), through the end face at up to 2.5mm|0.10" and are reliable through millions of operations. Optional magnetic targets can be used to further increase sensing range. Using the latest production methods and materials this product meets global certification requirements and its robust design makes it suitable for use in arduous and hazardous environments. Euroswitch products are also available with multi-approvals including combinations of the following global and regional certification standards; ATEX / IECEx Ex d (Ex db); Ex ia; UL & CSA Cl I Div 1 & 2 and Cl2 Div 1 & 2; EAC / TRCU; INMETRO; KCs; CCOE / PESO; ECAS ex; FM; JIS and NEPSI/CQST. Suitable for use in the design of safety functions up to SIL2 or SIL3, these proximity switches meet the requirements of IEC 61508:2010 Routes 1H & 1S with Systematic Capability (SC3) as an element/subsystem suitable for use in safety related systems performing safety functions up to and including SIL 2 with HFT=0 (1oo1) and SIL 3 with HFT =1 (1oo2).
- Körperform
- Zylindrisch mit LED-Anzeige
- Werkstoff Körper
- 316L-Edelstahl
- Kontakt-Anordnung
- SPCO / SPDT (Formular C)
- Kontakt-Material
- Palladium-Silber
- Montage-Gewinde
- 5/8"-18 UNF (52.56 mm / 2.07" long) c/w 2 x locknuts
- Maximaler Strom
- 250mA
- Verbindung
- Mini-Change Quick Disconnect 3 pin connector
- Conduit-Eintrag
- k. A.
- Beendigung
- Stecker V3
- Zertifizierung & Zulassungen
- UL Listed (Underwriters Laboratory)
- Gefährlicher Ort
- k. A.
- Gruppe Gas
- k. A.
- Gruppe Staub
- k. A.
- Temperaturklasse (T-Bewertung)
- T4
- Betriebstemperatur
- -40°C bis +60°C / -40°F bis +140°F
- Erfassungsbereich mit Magnet
- <12mm (0.47")
- Bewertung des Sensorflächendrucks
- 2000psi / 138 bar
- Umweltschutz
- IP 66 & 67 / NEMA 4X & 6P
- Sicherheitseinstufung
- SIL 2 / SC3
- Reichweite (eisenhaltiges Ziel)
- 2,5 mm|0,10"
- Wiederholbarkeit
- Ungefähr 0,05 mm (0,002")
- Reaktionszeit
- 8 ms
- Differential/Hysterese
- < 0.51mm (0.020")
Alle unsere Produkte sind auch als Ordinary Location / General Industrial erhältlich.
| Dokument | Sprache |
|---|---|
| Installations- und Betriebsanleitung |
|
| Installations- und Betriebsanleitung |
|
| Installations- und Betriebsanleitung |
|
| Installations- und Betriebsanleitung |
|
| Installations- und Betriebsanleitung |
|
| Installations- und Betriebsanleitung |
|
| Installations- und Betriebsanleitung |
|
| Installations- und Betriebsanleitung |
|
Alternative Versionen verfügbar
| Feature | Variation | Verwandte Produktseite |
|---|