Proximity Switch - Ferrous » FS-CYL-B Series
Hazardous Area Prox Switch - UL & CSA Class I II III Divison 1, Zone 1 Grps Grps A B C D / Grps E F G - T4A - NEMA 7 & 9 - Single Pole Change Over - 316L Stainless Steel
Certifications / Approvals
Proximity Switch Certified for UL & CSA Class I II III Divison 1, Zone 1 Groups Grps A B C D / Grps E F G T4A Rated for use in Gas & Dust Class I II III Div 1 NEMA 7 & 9
This Proximity Switch has a 316L Stainless Steel housing with SPCO / SPDT (Form C) , volt free Palladium-Silver contacts. It has a maximum switching current of 4A and can be used for switching multiple voltages in AC or DC. These switches are able to sense ferrous material, such as carbon steel or stainless steel (17/4 or 400 series), through the end face at up to 2.3mm|0.09" and are reliable through millions of operations. Optional magnetic targets can be used to further increase sensing range. Meeting global certification requirements, their robust design makes them suitable for use throughout Class I & II Division 1 environments. Their fully encapsulated and dust-tight NEMA Type 7 & 9 construction makes them a reliable and proven alternative to mechnical (lever arm or roller) type limit switches with a much improved life expectancy in the following hazardous area designations: NEMA 7 Gas (Div. 1 & 2, Class I, Groups B, C, & D) and NEMA 9 Dust (Div. 1 & 2, Class II, Groups E, F, & G). Euroswitch products are also available with multi-approvals including combinations of the following global and regional certification standards; ATEX / IECEx Ex d (Ex db); Ex ia; UL & CSA Cl I Div 1 & 2 and Cl II Div 1 & 2; NEMA 7 & 9; EAC / TRCU; INMETRO; KCs; CCOE / PESO; ECAS ex; FM; TIIS, JIS and NEPSI/CQST. Please contact us for more information.
- Body Material
- 316L Stainless Steel
- Contact Arrangement
- SPCO / SPDT (Form C)
- Contact Material
- Palladium-Silver
- Mounting
- Flange with 31.75mm [1.250"] probe length
- Max Current
- 4A
- Connection
- PVC Leads
- Conduit Entry
- 1/2" NPT
- Termination
- Lead wires with Earth
- Certification & Approvals
- UL & CSA (Underwriters Laboratory & Canadian Standards Association)
- Hazardous Location
- Class I II III Div 1
- Gas Group
- Grps A B C D
- Dust Group
- Grps E F G
- Temperature Class (T Rating)
- T4A
- Operating Temperature
- -40°C to +100°C / -40°F to +212°F
- Sensing Range with Magnet
- <12mm (0.47")
- Sensing Face Pressure Rating
- 3000psi / 207 bar
- Environmental Protection
- IP 66, 67 & 68 (24hrs at 30m)/ NEMA 4X & 6P
- Safety Rating
- SIL 2 / SC3
- Actuation
- Ferrous Actuated (Magnet Optional)
- Range (ferrous target)
- 2.3mm|0.09"
- Repeatability
- Approx. 0.05mm (0.002")
- Response Time
- 8 ms
- Differential / Hysteresis
- < 0.51mm (0.020")
All of our products are also available as Ordinary Location / General Industrial.
Document | Language |
---|---|
Installation and Operating Instructions | English |
Installation and Operating Instructions | Spanish |
Installation and Operating Instructions | Italian |
Installation and Operating Instructions | German |
Installation and Operating Instructions | Russian |
Installation and Operating Instructions | Portuguese |
Installation and Operating Instructions | French |
Installation and Operating Instructions | Chinese |